How to Size an Inverter for a Load Profile with Peak Spikes

Avoid Undersizing in Real-World Scenarios with Air Conditioners, Pumps, and Compressors


The “Peak Problem” Most System Buyers Ignore

When designing or procuring a solar + storage system, it’s common to calculate inverter size based on average daily load — 3kWh, 5kWh, maybe 10kWh per day.

But average use is not the problem. Peaks are.

Air conditioners, water pumps, fridges, and even small compressors can cause short, high-current startup surges that stress inverters beyond their rated capacity.

If you ignore these spikes, the inverter may trip, shut down, or fail prematurely — even when the battery or solar system still has plenty of energy available.

So how do you size for them — without overpaying for an oversized inverter?


1. Understanding Load Profiles: More Than Just kWh

Many first-time system buyers think in terms of energy:

“I consume about 7kWh per day, so a 5kW inverter with a 10kWh battery should be fine.”

But energy (kWh) is different from power (kW):

MetricMeaningWhy It Matters
kWhTotal energy consumed over timeFor sizing batteries & PV
kW (or W)Instantaneous power drawFor sizing inverters
Peak WattShort bursts of high power (1–3 seconds)For startup loads

A 2HP air conditioner may have a rated draw of 1.5kW but spike to 3–4kW at startup.
If your inverter is rated only 2kW, it will either:

  • Shut off (to protect itself)
  • Enter overload protection mode
  • Or allow the load, then overheat over time

Sizing must be based on peak needs, not just average.


2. Common Loads That Cause Power Spikes

Here’s a list of common devices that can cause inrush current or spike loads:

ApplianceNormal Running LoadStartup / Spike Load
Refrigerator (300L)~150WUp to 600–800W (motor surge)
Air Conditioner (1.5HP)~1.5kWUp to 3–4kW spike
Water Pump (0.75kW)~750W~1.5–2.2kW surge
Washing Machine~500–700W2–3× surge when motor starts
Freezer Chest~100W500–600W spike
Small Power Tools500–1000WUp to 2–2.5kW surge

These loads often spike for 0.5 to 3 seconds — not long, but long enough to trip protection circuits in undersized inverters.


3. Key Inverter Specs You Should Understand

Not all 5kW inverters are equal. When evaluating inverter specs for spiky loads, focus on:

Inverter SpecWhat It Means
Rated Output PowerThe continuous power it can handle (e.g., 5kW)
Surge PowerThe short-duration peak it can support (e.g., 2× for 5 sec)
Overload ToleranceAbility to handle overdraw without shutdown
AC Bypass / Grid AssistWhether the grid can carry spikes if inverter is small

Some high-quality hybrid inverters can handle 1.5× to 2× their rated power for 5–10 seconds — crucial for handling startup surges.


4. Step-by-Step: How to Size Inverter with Peak Loads

✅ Step 1: List All Loads

Identify all devices that may run simultaneously, and note both their rated and potential startup draws.

Example:

ApplianceRated PowerStartup Surge
Fridge150W800W
Air Conditioner1.5kW3.5kW
Water Pump0.75kW1.8kW
LED Lighting200W
Router + TV150W

Total Running Load: ~2.75kW
Worst-Case Simultaneous Surge: 5.5–6kW

✅ Step 2: Check Surge Tolerance of Candidate Inverters

Look for inverter models that offer:

  • Surge rating of 2× rated output for 5 seconds
  • Fast-switching MOSFET or IGBT design
  • Good THD (<3%) under surge
  • Effective BMS or EMS integration for overload response

✅ Step 3: Apply a 20–30% Safety Margin

If your worst-case spike is 6kW, a 5kW inverter with 2× surge (10kW) is ideal.
But if using an inverter with only 1.5× surge, you may need to go up to 6kW rated size.

Also consider future appliances — will the owner add a second pump, bigger fridge, or EV charger later?

It’s safer to oversize slightly — especially in off-grid setups.


5. Special Considerations for Off-Grid and Hybrid Systems

In off-grid setups, the inverter is the only source of AC power — no backup from the grid.

So it must:

  • Handle every spike and sustained load
  • Switch between charging and discharging instantly
  • Maintain voltage stability under dynamic loads

That’s why:

  • Surge capacity is more important off-grid
  • Pure sine wave output is critical for inductive loads
  • Parallel inverter support may offer a solution (see below)

6. When to Use Parallel Inverters

In cases where a single inverter cannot handle the expected surge (or redundancy is needed), consider a parallel setup.

Example:

  • Two 5kW hybrid inverters
  • Shared load, shared battery bank
  • Configured with master/slave or parallel logic

This allows:

  • Better load sharing during spikes
  • Redundancy if one inverter fails
  • Easier scaling in small commercial projects

Note: Parallel inverters must be communication-compatible (CAN, RS485) and use identical firmware. Proper load balancing and wiring are essential.


7. Bonus Tip: Use Soft-Start Devices or Sequenced Load Activation

Sometimes, the answer isn’t a bigger inverter — it’s smarter load control.

Options include:

  • Soft-start relays or VFDs on pumps and compressors
  • Smart load sequencing via EMS: stagger appliance startup by 5–10 seconds
  • Load-priority configuration in hybrid inverter settings

These measures reduce the chance of multiple devices spiking at the same time, allowing a smaller inverter to survive spikes effectively.


Real-World Example: Villa Project in Coastal Vietnam

A solar installer was designing a 10kWh battery + hybrid inverter system for a villa with:

  • 1 AC unit
  • 1 refrigerator
  • 1 well pump
  • 10 lights
  • 1 smart TV

Client insisted a 3.5kW inverter would be enough based on daily energy.

But field load testing showed:

  • AC + pump startup = 5kW momentary draw
  • The 3.5kW inverter tripped during parallel start

Solution:

  • Upgraded to 5kW inverter with 2× surge (10kW)
  • Configured AC and pump start delay via EMS
  • Result: Stable power, no shutdowns

Don’t Let Peak Spikes Undermine a Good System

A beautifully designed solar + battery system can be ruined by one thing:

An undersized inverter that fails under startup load.

To avoid that:

  • Understand which loads spike and by how much
  • Choose inverters with generous and well-documented surge capacity
  • Apply a margin of safety in both power and duration
  • Use control tools when necessary to reduce concurrent spikes

With the right sizing logic, your system will run smoother, last longer, and avoid the most frustrating type of failure: one that was preventable from the start.


Recently Published

相关文章

开始在上面输入您的搜索词,然后按回车进行搜索。按ESC取消。